Short answer

Heat tape keeps exposed water pipes from freezing. Constant-wattage cable puts out a fixed heat (7 W/ft on one common kit) and uses a thermostat; self-regulating cable (3 W/ft at 50°F) adjusts itself. Run it straight along the pipe, on a GFCI, under nonflammable insulation.

What we did: We set three kinds of pipe heat cable side by side using each maker's own rules, worked out running costs with EIA's latest electricity price, and priced five products on one day.

⚠️ Fire risk. CPSC estimated about 1,500 fires, 10 deaths and 100 injuries a year from faulty heat tapes (1996 release). CPSC rules: plug into a GFCI-protected outlet; “Do not wrap heat tape over itself unless specifically permitted”; put tape on the pipe, “never on top of the insulation”; inspect every year and replace any tape with cracked, charred or bare spots. Don’t use an extension cord unless the maker allows one.

Three kinds of heat tape

The rules change by type. Read your product’s sheet before you start.

Constant-wattage, built-in thermostat Self-regulating Constant-wattage, no thermostat
Example Frost King HC kits Raychem Frostex EasyHeat HB
Heat output 7 W/ft, fixed 3 W/ft at 50°F; more as the pipe gets colder Fixed
Turns on/off On below 38°F, off above 45°F Always on when plugged in; output drops as it warms Needs a separate thermostat, or someone watching a pilot light
Pipe types Water-filled plastic or metal supply pipes Metal or plastic pipe and tubing Metal water pipes only; outdoor only
How it goes on Flat and straight; never wrapped or spiraled Straight runs along the pipe, not spiraled Spiral or straight per its table; turns at least 1/2 in. apart; never touching or crossing
Insulation 1/2 in. fiberglass or other nonflammable insulation with vapor seal 1/2 in. or thicker fire-retardant, waterproof insulation Never insulate or overwrap
Length Follow the chart; “do not oversize the cable” Max 50 ft per plug Never cut or shorten
Ground-fault protection Plug light; check the GFCI if dark 27 mA ground-fault unit built into the plug GFCI required

Overlap rules depend on the maker: Frost King says “Never ever overwrap,” and EasyHeat HB must never touch or cross itself.

Before you buy

  1. Measure the pipe. Length plus its outside diameter. Frost King’s chart covers 3/8–3/4 in. and 1–1-1/2 in. pipe; buy the size it lists. Frost King: “do not oversize the cable.”
  2. Check the pipe material. HB-type cable is metal only. Frost King says plastic only if it is a primary supply pipe and not PVC. Frostex allows plastic.
  3. Check how cold it gets. Frostex’s table adds a second run of cable, or thicker insulation, for colder design temperatures and larger pipe.
  4. Check the outlet. Grounded, 3-prong, 120 V, GFCI-protected.

Install basics

Power off and cable unplugged until the last step.

  1. File off sharp edges. Remove any old heat tape and insulation first (Frostex, EasyHeat).
  2. Lay the cable straight along the pipe, as your sheet shows.
  3. Tape it down with tape rated at least 176°F (Frost King); EasyHeat HB says every 6 inches. No wire or metal clamps (Frostex, EasyHeat).
  4. Thermostat bulb, if any, against the pipe, per the sheet. CPSC: check whether it is covered by insulation or left uncovered.
  5. Cover with the insulation the maker specifies. Keep the plug and end seal dry and off the ground.
  6. Plug in. Test: Frost King says to put an ice bag on the thermostat for about 20 minutes; the cable should then feel warm.

Do not use pipe heat cable on buried pipe, drain lines, fuel lines, hoses, gutters or roofs (Frost King, Frostex, CPSC).

How long to run it

Product type Maker’s rule
Thermostat kit (Frost King) Leave plugged in through the cold season; it switches on below 38°F and off above 45°F
Self-regulating (Frostex) “Can be left plugged in all year”; unplug when there’s no freeze risk to save energy
No-thermostat (EasyHeat HB) Never energize above 50°F; turn off at the end of the season

Check the indicator light and the GFCI at the start of winter and after any trip.

What it costs to run

Formula:

kWh = watts per foot × feet × hours ÷ 1,000 Cost = kWh × your electricity price

EIA’s U.S. average residential price was 18.31¢ per kWh in July 2026 (released 2026-09-24). Use the rate on your own bill if you have it.

Example (our arithmetic) Watts Hours kWh Cost at 18.31¢
12 ft Frost King kit (7 W/ft), on all 30 days of a month 84 W 720 60.5 $11.07
50 ft Frostex (3 W/ft at 50°F), plugged in 30 days 150 W 720 108 $19.77

These are full-time worst cases. A thermostat kit runs only below 38–45°F. Self-regulating cable uses more than its 50°F rating when the pipe is colder (Frostex output graph), and less when warmer.

What heat tape costs

Zoro list prices, checked 2026-10-17.

Product Length Type Price
Frost King HC12A 12 ft Constant-wattage, thermostat $34.39
EasyHeat AHB112A 12 ft Pre-assembled water-pipe cable $40.45
EasyHeat Freeze Free 10815 15 ft Self-regulating $56.55
EasyHeat Freeze Free 2102 100 ft bulk, 3 W Self-regulating; needs a plug kit $253.99 · $267.99 (two listings)
EasyHeat Freeze Free 10802 30 in. connection kit Plug kit for bulk cable $29.45

When heat tape isn’t enough

Wiring a new outlet or circuit in a pump house is a job for a licensed electrician.

FAQ

How does heat tape work? Constant-wattage tape puts out the same heat all the time and relies on a thermostat. Self-regulating cable changes its output with temperature.

What is self regulating heat tape? A heating cable with a conductive core that changes its heat output with temperature: more heat as the pipe gets colder, less as it warms. Raychem rates Frostex at 3 W/ft at 50°F. It needs no thermostat, but still needs ground-fault protection and insulation.

Does heat tape use a lot of electricity? Multiply watts per foot by feet and hours, divide by 1,000, then multiply by your electric rate. A 12 ft, 7 W/ft cable on all month uses about 60 kWh, roughly $11 at EIA’s July 2026 average of 18.31¢/kWh. A thermostat cuts that.

Sources

All sources checked 2026-10-17.

Method: product rules are quoted from each maker’s own sheet. Safety rules come from CPSC’s heat-tape releases (1990 and 1996; CPSC’s fire estimates are from those years). Running costs are our arithmetic using EIA’s July 2026 average residential price. Prices are Zoro list prices from 2026-10-17. We have not installed or tested heat tape ourselves.

Editorial note: This page was researched and fact-checked by the County Road Home team against the manufacturer documents and public sources listed above. AI tools assisted with drafting; every number was checked by an editor before publishing. We are not licensed electricians. For new outlets or circuits, use a licensed electrician. Found an error? Email hello@countyroadhome.com and we will review it within 7 days. Last checked: 2026-10-17.