Short answer

Common well pressure switch settings are 20/40, 30/50 and 40/60 psi, each with a 20 psi differential. First set the empty tank's precharge 2 psi below the new cut-in: 28 psi for 30/50, 38 psi for 40/60. About 3½ range-nut turns shift both points 10 psi.

What we did: We worked out the tank drawdown for each common switch setting and checked it against Amtrol's published tank figures.

⚠️ Safety first. The switch terminals carry 115 V or 230 V. Turn the pump breaker off before you remove the cover, and check the terminals with a non-contact tester or meter. Franklin warns that contact with hazardous voltage “could result in death or serious injury”. Amtrol says to turn off pump power and release all water pressure before working on the tank, and that only qualified professionals should check or re-charge tank precharge. Not comfortable? A licensed pump installer or electrician can do it in one visit.

A blue bladder pressure tank with a pressure switch on outdoor wellhead plumbing in dry grass, with a house behind A pressure tank and pressure switch at an outdoor wellhead in rural California. Photo: Goldrath, U.S. Geological Survey (public domain).

What the numbers mean

“40/60” means the pump starts (cut-in) at 40 psi and stops (cut-out) at 60 psi. The gap is the differential. Precharge is the air pressure in the tank, read with the tank empty of water (Amtrol). Range is the span the cut-out can be set within, e.g. 20–65 psi on a Square D 9013FSG2.

20/40 vs 30/50 vs 40/60

Three views of a 20-gallon pressure tank on a 40/60 switch: empty at 38 psi, 5.9 gallons when the pump stops at 60 psi, 0.7 gallons when it restarts at 40 psi

Our drawing. Volumes computed with Boyle’s law (absolute pressure = gauge + 14.7) for a 20-gallon tank, precharge 2 psi below cut-in; tank shape simplified.

Higher settings: stronger pressure, but less water between pump starts.

Setting Differential Tank precharge (cut-in − 2 psi) Drawdown factor, our Boyle’s-law calc Factor implied by Amtrol’s published drawdown Amtrol drawdown, 20 gal tank (WX-202) Amtrol drawdown, 44 gal tank (WX-250)
20/40 20 psi 18 psi 0.34 Not published in the Amtrol sheets checked — —
30/50 20 psi 28 psi 0.30 0.31 6.2 gal 13.6 gal
40/60 20 psi 38 psi 0.26 0.27 5.4 gal 11.8 gal
50/70 20 psi 48 psi 0.23 0.235 4.7 gal 10.4 gal

Step 1: Set the tank precharge

Amtrol: set precharge “2 psig below the pressure switch pump cut-in setting” (Square D gives the same rule). Change the switch without this and the tank delivers less water per cycle.

  1. Turn off power to the pump at the breaker.
  2. Open a faucet and drain the tank. Amtrol: “Make adjustments only when the tank is empty of water and the system is off”.
  3. Read the air valve with a tire gauge.
  4. Add air (bike pump or compressor) or let air out until it reads 2 psi below the new cut-in.

Do not add air if the tank has lost air before, shows corrosion, or the pump short-cycles more than when new. Amtrol warns re-pressurizing such a tank “could result in rupture or explosion”. Replace it. Water from the air valve means a leaking bladder; see pump troubleshooting.

Step 2: Adjust a Square D 9013FSG2

The catalog number’s end code is the factory setting: J20 = 20/40, J21 = 30/50, J24 = 40/60.

Square D limits: cut-out 20–65 psi (34–65 with M4), cut-in 5–45 psi (19–45 with M4), differential 15–30 psi, maximum 65 psi; motor up to 1.5 HP at 115 V, 2 HP at 230 V.

40/60 fits; 50/70 does not. Square D: pressure “should never exceed the upper limit of the range” (it shortens diaphragm life). For higher settings, fit a switch with the right range, such as the 9013FYG (25–80 psi cut-out).

Both nuts take a 3/8-inch nut driver or socket.

Nut Turn clockwise Turn counterclockwise Effect
Range nut (R) Raises cut-in Lowers cut-in Cut-out moves by the same amount; differential stays the same
Differential nut (D) Raises cut-out Lowers cut-out Cut-in does not change
From To Turn range nut clockwise
20/40 30/50 3½ turns
30/50 40/60 3½ turns
20/40 40/60 8 to 8½ turns

Roughly 3 psi per turn, not exactly linear. Finish by the gauge.

Steps:

  1. Watch the gauge through one cycle. Note where the pump starts and stops.
  2. Turn off the pump breaker. Remove the switch cover. Check for water leaking at the diaphragm or flange and for frayed wires.
  3. Set the tank precharge for the new cut-in (Step 1).
  4. To move both points: turn the range nut clockwise to raise, counterclockwise to lower.
  5. To change only the cut-out: turn the differential nut.
  6. Replace the cover, restore power, run a faucet until the pump starts, close it, note where it stops. Adjust in small steps.

Square D: do not sand, file or chemically clean pitted contacts. If the switch won’t respond, check its pressure port for silt or lime.

Pump won’t shut off after raising it?

Each psi costs the pump 2.31 feet of head (Amtrol); 30/50 → 40/60 adds 23.1 feet. A worn or undersized pump stalls below cut-out and runs nonstop, moving little water. Franklin’s 4-inch motors (2 hp and smaller) need cooling flow “greater than zero”.

Switch with a side lever (Form M4)

An M4 switch has a side lever. It shuts the pump off if pressure drops about 10 psi below cut-in, e.g. when the well runs low (Square D). That point follows the cut-in.

FAQ

What should my pressure tank be set at for 40/60? 38 psi, read with the tank empty and the pump off. The rule is 2 psi below cut-in: 28 psi for 30/50, 18 psi for 20/40.

How many turns to go from 30/50 to 40/60? About 3½ clockwise turns of the range nut, per Square D’s guideline; 8 to 8½ turns from 20/40 to 40/60. Treat it as a start and finish with the gauge.

Is 40/60 better than 30/50? About 10 psi more at the taps, but roughly 13% less water per cycle, and the pump needs 23 more feet of head. Only if your pump has head to spare.

Sources

All sources checked 2026-10-05.

Method: we combined Square D’s switch ranges, pressure codes, turn counts and M4 behavior with Amtrol’s precharge rules and drawdown volumes into one settings table. We calculated drawdown factors with Boyle’s law (absolute pressure = gauge + 14.7), set them next to factors back-calculated from Amtrol’s published drawdowns, and explained the gap. We also checked the pump-side limits in Franklin’s manuals and converted switch pressure to feet of head. Page references are in the sources above. We have not adjusted or tested these switches ourselves.

Editorial note: This page was researched and fact-checked by the County Road Home team against the manufacturer documents and public sources listed above. AI tools assisted with drafting; every number, spec and rule was checked by an editor before publishing. We are not licensed well contractors or electricians — for electrical, gas and water-safety work, use a licensed professional. Found an error? Email hello@countyroadhome.com and we will review it within 7 days. Last checked: 2026-10-05