Well pump wire size calculator

Short answer: For a 1 hp, 230 V submersible pump, 12 AWG copper covers up to 400 ft of total cable, 10 AWG 630 ft and 8 AWG 990 ft, counted from the power supply to the motor at 5% voltage drop. A 115 V 1/2 hp pump allows only 160 ft on 12 AWG.

What we did: We turned Franklin Electric's cable-length table into a lookup that also handles two wire sizes in one run.

Last checked October 5, 2026 · By the County Road Home team

Turn off the pump circuit at the breaker and confirm it is dead with a tester before touching any well wiring.

Have a licensed electrician or licensed pump installer size and install the wire, follow the National Electrical Code and your local code, and ground the motor and all nearby metal with wire no smaller than the motor cable (AIM p.10). These lengths are for Franklin 4-inch motors; other makers' motors draw different amps, so use the table in their manual.

Your pump motor

On the control box label, the motor nameplate or the installer's invoice.

A 3-wire motor has a separate control box near the tank or panel. No control box: 2-wire. Not sure is fine: the wire table is the same for both.

On the control box label or the installer's invoice.

Total cable length

How deep the pump hangs. The installer's invoice or your well record often lists it.

Pace off the buried run from the house to the well, plus the wire inside the house to the panel.

Options

Not sure? Keep 5%, the table's own basis.

Jacketed = all wires in one outer cover. Not sure? Keep jacketed: it never gives a smaller size.

How the calculator works

Well pump wire size chart (4-inch, single-phase, copper)

Maximum total cable length in feet, power supply to motor, 75 °C copper, 5% voltage drop. From AIM 2026, p.50. Multiply by 0.6 for 3%.

VoltsHP1412108643210000000000
1151/21001602503906209601,1901,4601,7802,1602,6303,1403,770
2301/24006501,0201,6102,5103,8804,8105,8807,1708,720–––
2303/43004807601,2001,8702,8903,5804,3705,3306,4707,8709,380–
23012504006309901,5402,3802,9603,6104,4105,3606,5207,7809,350
2301.51903104807701,2001,8702,3202,8503,5004,2805,2406,3007,620
23021502503906209701,5301,9102,3602,9303,6204,4805,4706,700
2303120*1903004707501,1901,4901,8502,3202,8903,6104,4705,550
23050110*1802804507108901,1101,3901,7402,1702,6803,330

0, 00, 000, 0000 = 1/0, 2/0, 3/0, 4/0. * Shaded in the manual: individual conductors only. 0 = printed as 0; "–" = no value printed. The table is titled '2-Lead and 3-Lead' and gives one row per voltage and horsepower, so a 1 hp 230 V 2-wire motor and a 1 hp 230 V 3-wire motor get the same lengths. A table from another motor maker may give different numbers; use the one for the motor actually installed.

Worked examples

One size: 1.5 hp, 230 V, pump at 260 ft, well head 120 ft from the panel → 380 ft total. 12 AWG allows 310 ft (too short), 10 AWG 480 ft, so 10 AWG. At 3% drop: 8 AWG (462 ft).

Two sizes (Franklin's example): 160 ft of existing #10 copper, new 3 hp 230 V motor at 310 ft.

SectionLength (ft)Max for size (ft)FractionTotalResult
#10 buried1603000.533——
+ #8 drop cable3104700.6601.193Over 1.00: too small
+ #6 drop cable3107500.4130.946Meets the limit

When this chart does not apply

Related

Frequently asked questions

What size wire do I need for a 1 hp well pump?

For a 1 hp, 230 V single-phase 4-inch motor, Franklin's table allows up to 400 ft of 12 AWG copper, 630 ft of 10 AWG and 990 ft of 8 AWG, from the power supply to the motor.

Can I use aluminum wire for a well pump?

Franklin allows it only two sizes larger than the copper size in the table, with oxidation inhibitor on every connection. Where the table calls for 12 AWG copper, you need 10 AWG aluminum.

Do I measure wire length from the panel or the well head?

From the power supply. Add the run from the panel to the well head and the drop cable down to the pump, not just the pump depth.

Sources

Method: Maximum lengths are copied from the '4-inch/1-Phase/2-Lead and 3-Lead/75 °C Cable' table of the Franklin Electric AIM Manual (2026 edition, p.50) and checked cell by cell against the PDF; the 3% option, aluminum rule, line-contactor limit and two-size method are the manual's own rules on pp.49–50. We have not installed or measured any pump wiring.